Voltage Drop Calculator
Long runs eat voltage. Motors run hot, lights dim and EV chargers throttle back — and the fix is usually one wire size up. Enter the load, the one-way distance and the conductor, and this calculator shows the drop in volts and percent, the voltage your equipment actually gets, and the smallest wire that brings the run under the 3% guideline.
Voltage Drop Calculator
Results
Voltage drop
7.90 V
Drop %
6.58 %
Voltage at load
112.10 V
Above the 5% total guideline — upsize the conductor
Recommended conductor for ≤3%
8 AWG
How It Works
Voltage drop is calculated with the NEC Chapter 9 method: VD = (2 × K × I × D) / CM for single-phase (1.732 in place of 2 for three-phase). K is the conductor resistivity constant — 12.9 for copper, 21.2 for aluminium — I is the load in amps, D the one-way distance in feet, and CM the conductor's circular mils. The NEC's informational notes recommend no more than 3% drop on a branch circuit and 5% total for feeder plus branch (NEC 210.19(A) Informational Note No. 4) — recommendations, not mandates, but the numbers good installations are designed to.
Worked Example
A 20-amp load, 100 feet from the panel, on 12 AWG copper at 120 volts: VD = (2 × 12.9 × 20 × 100) / 6,530 = 7.90 volts — a 6.59% drop, leaving 112.10 volts at the load. That fails the 3% guideline. The calculator's recommendation: 8 AWG, which drops 3.13 volts (2.60%) and passes.
Reference Table
Conductor circular mils (NEC Chapter 9 Table 8 basis):
| Conductor | Circular mils |
|---|---|
| 14 AWG | 4,110 |
| 12 AWG | 6,530 |
| 10 AWG | 10,380 |
| 8 AWG | 16,510 |
| 6 AWG | 26,240 |
| 4 AWG | 41,740 |
| 3 AWG | 52,620 |
| 2 AWG | 66,360 |
| 1 AWG | 83,690 |
| 1/0 AWG | 105,600 |
| 2/0 AWG | 133,100 |
| 3/0 AWG | 167,800 |
| 4/0 AWG | 211,600 |
| 250 kcmil | 250,000 |
| 300 kcmil | 300,000 |
| 350 kcmil | 350,000 |
| 400 kcmil | 400,000 |
| 500 kcmil | 500,000 |
K = 12.9 for copper, 21.2 for aluminium (Ω·circular mil per ft).
Frequently Asked Questions
What voltage drop is acceptable?
The NEC recommends — as an informational note, not a rule — a maximum of 3% on a branch circuit and 5% combined for feeder and branch. Equipment manufacturers may specify tighter limits; check the nameplate.
Do I enter the round-trip distance?
No. Enter the one-way distance from source to load. The formula's factor of 2 already accounts for the return conductor.
Why does aluminium drop more than copper?
Aluminium's resistivity constant (K = 21.2) is higher than copper's (12.9), so the same size drops more voltage. Aluminium runs typically go one to two sizes larger.
Does voltage drop waste energy?
Yes — dropped voltage becomes heat in the conductor. It is usually a small cost, but on long, heavily loaded runs it adds up over the year.