Toolbox Calculator

Voltage Drop Calculator

Long runs eat voltage. Motors run hot, lights dim and EV chargers throttle back — and the fix is usually one wire size up. Enter the load, the one-way distance and the conductor, and this calculator shows the drop in volts and percent, the voltage your equipment actually gets, and the smallest wire that brings the run under the 3% guideline.

Voltage Drop Calculator

Material
Phase

Results

Voltage drop

7.90 V

Drop %

6.58 %

Voltage at load

112.10 V

Above the 5% total guideline — upsize the conductor

Recommended conductor for ≤3%

8 AWG

How It Works

Voltage drop is calculated with the NEC Chapter 9 method: VD = (2 × K × I × D) / CM for single-phase (1.732 in place of 2 for three-phase). K is the conductor resistivity constant — 12.9 for copper, 21.2 for aluminium — I is the load in amps, D the one-way distance in feet, and CM the conductor's circular mils. The NEC's informational notes recommend no more than 3% drop on a branch circuit and 5% total for feeder plus branch (NEC 210.19(A) Informational Note No. 4) — recommendations, not mandates, but the numbers good installations are designed to.

Worked Example

A 20-amp load, 100 feet from the panel, on 12 AWG copper at 120 volts: VD = (2 × 12.9 × 20 × 100) / 6,530 = 7.90 volts — a 6.59% drop, leaving 112.10 volts at the load. That fails the 3% guideline. The calculator's recommendation: 8 AWG, which drops 3.13 volts (2.60%) and passes.

Reference Table

Conductor circular mils (NEC Chapter 9 Table 8 basis):

ConductorCircular mils
14 AWG4,110
12 AWG6,530
10 AWG10,380
8 AWG16,510
6 AWG26,240
4 AWG41,740
3 AWG52,620
2 AWG66,360
1 AWG83,690
1/0 AWG105,600
2/0 AWG133,100
3/0 AWG167,800
4/0 AWG211,600
250 kcmil250,000
300 kcmil300,000
350 kcmil350,000
400 kcmil400,000
500 kcmil500,000

K = 12.9 for copper, 21.2 for aluminium (Ω·circular mil per ft).

Frequently Asked Questions

What voltage drop is acceptable?

The NEC recommends — as an informational note, not a rule — a maximum of 3% on a branch circuit and 5% combined for feeder and branch. Equipment manufacturers may specify tighter limits; check the nameplate.

Do I enter the round-trip distance?

No. Enter the one-way distance from source to load. The formula's factor of 2 already accounts for the return conductor.

Why does aluminium drop more than copper?

Aluminium's resistivity constant (K = 21.2) is higher than copper's (12.9), so the same size drops more voltage. Aluminium runs typically go one to two sizes larger.

Does voltage drop waste energy?

Yes — dropped voltage becomes heat in the conductor. It is usually a small cost, but on long, heavily loaded runs it adds up over the year.

Safety Note

These calculators are planning and estimating aids based on the NEC references shown. They are not a substitute for the current NEC, local amendments, or a licensed electrician. Verify every result before ordering material or energising a circuit.

Related Calculators