Wire Size Calculator
Wire size is not a guess: too small overheats, too big wastes money on every foot. Enter the load in amps, tell it whether the load runs three hours or more, and this calculator picks the smallest conductor that NEC Table 310.16 allows — with the small-conductor limits of NEC 240.4(D) applied and the matching breaker size shown.
Wire Size Calculator
Optional — voltage-drop check
Results
Recommended conductor size
12 AWG
Ampacity of selected size
25 A
Maximum breaker size
20 A
Based on NEC Table 310.16, 75°C copper, with NEC 240.4(D) small-conductor limits applied.
How It Works
The calculator takes your design current — the load, increased by 25% for continuous loads as NEC 210.19(A)(1) requires — and finds the smallest conductor in Table 310.16 whose ampacity at your insulation temperature rating covers it. It then applies the 240.4(D) caps (14 AWG copper max 15 A, 12 AWG max 20 A, 10 AWG max 30 A), which is why a 20-amp load returns 12 AWG even though 14 AWG's table ampacity reads 20. Ampacity is only half the job on long runs — add your distance and voltage and it checks voltage drop too.
Worked Example
An EV charger drawing 48 amps is a continuous load, so the design current is 48 × 1.25 = 60 amps. On copper at 75°C, 6 AWG (65 A ampacity) is the smallest conductor that covers 60 amps — result: 6 AWG, 60-amp breaker.
Wire Size Chart — Copper Ampacity (NEC 310.16)
NEC Table 310.16, 75°C column ampacity (amps):
| Copper | Amps |
|---|---|
| 14 AWG | 20 |
| 12 AWG | 25 |
| 10 AWG | 35 |
| 8 AWG | 50 |
| 6 AWG | 65 |
| 4 AWG | 85 |
| 3 AWG | 100 |
| 2 AWG | 115 |
| 1 AWG | 130 |
| 1/0 AWG | 150 |
| 2/0 AWG | 175 |
| 3/0 AWG | 200 |
| 4/0 AWG | 230 |
| 250 kcmil | 255 |
| 300 kcmil | 285 |
| 350 kcmil | 310 |
| 400 kcmil | 335 |
| 500 kcmil | 380 |
| Aluminium | Amps |
|---|---|
| 12 AWG | 20 |
| 10 AWG | 30 |
| 8 AWG | 40 |
| 6 AWG | 50 |
| 4 AWG | 65 |
| 3 AWG | 75 |
| 2 AWG | 90 |
| 1 AWG | 100 |
| 1/0 AWG | 120 |
| 2/0 AWG | 135 |
| 3/0 AWG | 155 |
| 4/0 AWG | 180 |
| 250 kcmil | 205 |
| 300 kcmil | 230 |
| 350 kcmil | 250 |
| 400 kcmil | 270 |
| 500 kcmil | 310 |
Frequently Asked Questions
Why did a 20-amp load give 12 AWG, not 14?
Table 310.16 lists 14 AWG copper at 20 A (75°C), but NEC 240.4(D) limits 14 AWG circuits to a 15-amp breaker. A 20-amp load therefore needs 12 AWG.
What is a continuous load?
A load expected to run at maximum current for three hours or more — EV charging, lighting, heating. The NEC requires conductors and breakers sized at 125% of it.
Can I use the 90°C column?
Only if every termination is rated 90°C, which is uncommon in residential work. The 75°C column is the safe default for most equipment; when in doubt, use it.
Does this cover aluminium branch wiring?
The table includes aluminium ampacities and 240.4(D) caps. Aluminium terminations have additional requirements (listed connectors, antioxidant where required) — follow the current NEC and local amendments.
What size wire do I need for a 60 amp circuit?
6 AWG copper. A 60 A breaker needs wire with an ampacity of at least 60 A at 75°C; 6 AWG copper is rated 65 A, the smallest size that qualifies. (This is why a 48 A EV charger on a 60 A breaker uses 6 AWG.)
What size wire do I need for a 100 amp circuit?
3 AWG copper. At 75°C, 4 AWG is rated 85 A — not enough for a 100 A breaker — while 3 AWG is rated exactly 100 A. For a 100 A sub-panel feeder this is the standard copper choice.
Safety Note
These calculators are planning and estimating aids based on the NEC references shown. They are not a substitute for the current NEC, local amendments, or a licensed electrician. Verify every result before ordering material or energising a circuit.