Duct Size Calculator
A duct too small whistles, starves the room and strains the blower. A duct too big wastes space and money. Enter the airflow in CFM and whether it is a trunk or a branch, and this calculator gives you the round size and the rectangular equivalent — with the one-size correction flex duct needs.
Results
Recommended round duct size
12 in
Computed diameter 11.06 in → rounded up
Rectangular equivalent (2:1)
16 × 8 in
CFM capacity of 12 in
471 CFM
at 600 fpm
How It Works
This calculator uses the velocity method behind the Manual D equal-friction approach: diameter = 13.54 × the square root of CFM divided by velocity — 900 feet per minute for trunk ducts, 600 for branches. The result rounds up to the next standard duct size. Rectangular sizes come from the Huebscher equation, which finds the rectangle with the same friction loss as the round duct. Flex duct is sized one size larger because compression and bends raise its resistance.
Worked Example
A branch carrying 400 CFM at 600 fpm needs a diameter of 13.54 × √(400 ÷ 600) = 11.06 inches — rounded up to a 12-inch round duct, or 16 × 8 inches rectangular at a 2:1 ratio.
Reference Table
Round duct size and the CFM it carries at branch velocity (600 fpm) and trunk velocity (900 fpm):
| Round size | CFM at 600 fpm (branch) | CFM at 900 fpm (trunk) |
|---|---|---|
| 4 in | 52 | 79 |
| 5 in | 82 | 123 |
| 6 in | 118 | 177 |
| 7 in | 160 | 241 |
| 8 in | 209 | 314 |
| 9 in | 265 | 398 |
| 10 in | 327 | 491 |
| 12 in | 471 | 707 |
| 14 in | 641 | 962 |
| 16 in | 838 | 1,257 |
Frequently Asked Questions
What is a ductulator?
A ductulator is the slide-rule or chart that converts airflow (CFM) into duct size at a chosen friction rate. This calculator does the same maths — velocity method, Manual D equal-friction equivalent — and adds the rectangular conversion.
Trunk or branch — which do I pick?
A trunk is the main duct leaving the air handler, sized at 900 fpm. A branch is the duct to a single room or register, sized at 600 fpm for quieter airflow.
Why is flex duct sized larger?
Flex duct compresses and sags, which raises friction. Sizing it one size up compensates — and keeping runs straight and fully extended matters as much as the size itself.
Round or rectangular — which is better?
Same friction loss, either works. Round is cheaper and quieter per CFM; rectangular fits in tight joist spaces. Pick by the space you have.