An undersized gas line starves every appliance on it — furnaces lock out, water heaters underperform, ranges lose their flame. Enter the total BTU of everything the run feeds and the longest distance from the meter, and this calculator returns the steel pipe size using the standard IFGC longest-length table.

Gas Pipe Sizing Calculator

Results

—

Longest-length method: every branch is sized from the total load and the longest run, per IFGC 402.4. For propane, CSST or pressures above 2 psi, capacities differ — this table is natural gas in steel pipe only.

How It Works

The longest-length method is deliberately conservative: you size the whole system as if the total load travels the full distance to the farthest appliance. Measure that run, round up to the next table length, add up every appliance's BTU rating, and the table gives the smallest pipe whose capacity covers the load at that length. The figures are the IFGC Table 402.4(2) capacities for natural gas in Schedule 40 steel at under 2 psi with a 0.5-inch water column pressure drop.

Worked Example

A furnace (80,000 BTU), tankless water heater (120,000 BTU) and range (65,000 BTU) total 265,000 BTU. The farthest appliance is 45 feet from the meter — round up to the 50-foot row. At 50 feet: ¾″ carries 151,000 (too small), 1″ carries 284,000 — result: 1-inch pipe, running at 93% of its table capacity.

Reference Table

IFGC Table 402.4(2) basis — natural gas, Schedule 40 steel, under 2 psi with a 0.5 in. w.c. drop. Capacity in thousands of BTU/hr:

Length (ft)½″¾″1″1¼″1½″2″
101723606781,3902,0904,020
201182474669571,4402,770
30951993747661,1522,217
40821723236649991,921
50731512845828761,685
75581212274667011,348
100501041954006021,158

Frequently Asked Questions

Why round the length up?

The table works in steps. A 45-foot run uses the 50-foot row because capacity only falls with distance — rounding down would understate the friction your gas actually meets.

Can I use this for propane?

No. Propane has different energy content and pressures, and its tables differ. This calculator is natural gas in steel pipe only; propane and CSST need their own tables.

What if appliances are added later?

Size for the future load now if you can — replacing an underground or in-wall gas run later costs far more than one pipe size today.

Who can install gas pipe?

In most jurisdictions only a licensed gas fitter or plumber, with a permit and pressure test. Treat this calculator as planning, not permission.

Safety Note

These calculators are planning and estimating aids based on the references shown. They are not a substitute for the current code, local amendments, or a licensed gas fitter or plumber. Verify every result before ordering material or starting work.