Box Fill Calculator

An overfilled box is a failed inspection and a heat problem waiting in the wall. This calculator applies NEC 314.16 exactly: every conductor, ground, clamp and device converted to cubic inches with the Table 314.16(B) allowances, so you know the smallest box that legally holds your splice before you close it up.

Box Fill Calculator

Entering conductors
Grounding conductors present
Internal clamps present

Results

Enter conductor counts to begin.

Total required volume

0.00 cu in

Selected box

4" square × 1½" deep — 18.0 cu in

How It Works

NEC 314.16 gives every element in a box a volume allowance based on conductor size — 2.00 cu in for 14 AWG, 2.25 for 12 AWG, up to 5.00 for 6 AWG. Conductors count once each. All the grounding conductors together count once. All internal clamps together count once. Each switch or receptacle counts twice, at the size of the largest conductor on it. Add the allowances and compare with the box's marked volume: the total must fit, with nothing left to "it'll probably be fine".

Worked Example

Four 12 AWG conductors enter a box with grounds, internal clamps and one receptacle: conductors 4 × 2.25 = 9.00, the grounds count once at 2.25, the clamps once at 2.25, and the device twice at 4.50 — total 18.00 cu in. That exactly fills a 4-inch square box 1½ inches deep (18.0 cu in). One more conductor and you would need the next box up.

Reference Table

Volume allowance per conductor (NEC Table 314.16(B)), cubic inches:

Conductor sizeAllowance (cu in)
18 AWG1.50
16 AWG1.75
14 AWG2.00
12 AWG2.25
10 AWG2.50
8 AWG3.00
6 AWG5.00

Frequently Asked Questions

Do pigtails count?

No. Conductors that originate inside the box and never leave it — pigtails to a device — are not counted under 314.16(B)(1). Only conductors entering or passing through count.

Why do all the grounds count as just one?

314.16(B)(5) counts all equipment grounding conductors together as a single allowance based on the largest one. (Note: recent NEC editions add a quarter allowance for each additional isolated ground — check your edition.)

The box isn't marked with a volume. Now what?

Use the standard volumes in NEC Table 314.16(A) for metal boxes — the common ones are in this calculator's box list. Plastic boxes are required to be marked with their volume.

What if I'm 0.5 cu in over?

Still a violation. Move up a box size, or use a box extension ring or a plaster ring whose marked volume adds to the total.

Safety Note