Residential Load Calculator

Adding a hot tub, a workshop or an EV charger? The first question is whether your service can carry the house you already have. This calculator runs the NEC dwelling load calculation both ways — the standard method of Article 220 and the optional method of 220.82 — and turns your loads into the only number that matters: the service size in amps. Electricians and inspectors also call this an electrical load calculator — same NEC Article 220 maths, whichever name you searched for.

Residential Load Calculator

Calculation method
4 or more fixed appliances (applies 75%)

Small-appliance circuits (2 × 1,500 VA) and laundry circuit (1,500 VA) are built in.

Results

Method

Standard Method (NEC 220)

Load breakdown

General lighting & receptacles (after demand)5,100 VA
Range (Table 220.55 demand)8,000 VA
Dryer (min 5,000 VA)5,000 VA
Water heater (100%)4,500 VA
HVAC (larger of heat/AC)4,800 VA
Total27,400 VA

Calculated amps

114.2 A

Recommended service size

125 A

How It Works

The standard method builds the load in layers: general lighting at 3 VA per square foot plus the two small-appliance circuits and laundry circuit the NEC requires, with the Table 220.42 demand factor (100% of the first 3,000 VA, 35% of the rest) because nothing in a house runs at once. The range takes its Table 220.55 demand, a dryer counts at least 5,000 VA, heating and cooling never run together so only the larger counts, and the largest motor adds 25%. The optional method of 220.82 is simpler — nameplate loads, 100% of the first 10 kVA and 40% of the remainder — and often gives a smaller, still code-compliant service. Both are shown so you can see the difference before an electrician quotes the upgrade.

Worked Example

A 1,500 sq ft home, 12 kW range, 5,000 VA dryer, 4,500 VA water heater, 4,800 VA air conditioning. Standard method: general load after demand 5,100 VA + range 8,000 + dryer 5,000 + water heater 4,500 + AC 4,800 = 27,400 VA = 114.2 amps → a 125-amp service. Optional method: the same house totals 23,000 VA = 95.8 amps → a 100-amp service passes. Same house, two legal answers — the optional method exists precisely for existing dwellings like this.

Frequently Asked Questions

Which method should I use?

The standard method always works. The optional method (220.82) is only for a dwelling served by a single service of 100 amps or more, and often gives a lower result. Your electrician and inspector decide which applies to your permit.

Why does the range count less than its rating?

Table 220.55 demand factors recognise that all elements of a range almost never run at full power together. A 12 kW range counts as 8,000 VA.

Heating or cooling — why not both?

A house heats or cools, never both at the same time, so the NEC counts only the larger of the two loads.

My result is between service sizes. What do I do?

Services come in standard sizes, so the calculator rounds up to the next one. If you plan an EV charger or hot tub later, tell your electrician now — upsizing during an upgrade is far cheaper than doing it twice.

Is a residential load calculation the same as an electrical load calculation?

Yes — "residential load calculation" is the NEC Article 220 term for the electrical load calculation of a dwelling. This page runs both the standard method (220.40–220.61) and the optional method (220.82) used for existing services.

Safety Note

These calculators are planning and estimating aids based on the NEC references shown. They are not a substitute for the current NEC, local amendments, or a licensed electrician. Verify every result before ordering material or energising a circuit.