Breaker Size Calculator
A breaker has one job: trip before the wire cooks. Size it from the load alone and you can still get it wrong — the wire sets the ceiling. Enter your load and the wire you plan to run, and this check returns the correct breaker and flags a mismatched pair before an inspector (or a fire) does.
Breaker & Wire Check
Results
—
How It Works
Continuous loads (3 hours or more) must be sized at 125% under NEC 210.19/215.2, so the breaker is the smallest standard size at or above 1.25 × the load. Then the wire check: NEC 310.16 gives each size an ampacity, and 240.4(D) caps breakers on small conductors — 15 A on 14 AWG, 20 A on 12 AWG, 30 A on 10 AWG — regardless of the insulation's temperature rating. The breaker must be big enough for the load and no bigger than the wire allows.
Worked Example
A 32 A continuous load needs 32 × 1.25 = 40 A, so a 40 A breaker. On 8 AWG copper (50 A ampacity, 50 A max breaker) the pair checks out. Run the same load on 10 AWG and it fails: the load still demands a 40 A breaker, but 10 AWG is capped at 30 A — the wire is the problem, not the breaker.
Reference Table
Copper ampacity (NEC 310.16, 75°C) and 240.4(D) max breaker:
| Wire | Ampacity (A) | Max breaker (A) |
|---|---|---|
| 14 AWG | 20 | 15 |
| 12 AWG | 25 | 20 |
| 10 AWG | 35 | 30 |
| 8 AWG | 50 | 50 |
| 6 AWG | 65 | 65 |
| 4 AWG | 85 | 85 |
| 3 AWG | 100 | 100 |
| 2 AWG | 115 | 115 |
| 1 AWG | 130 | 130 |
| 1/0 AWG | 150 | 150 |
| 2/0 AWG | 175 | 175 |
| 3/0 AWG | 200 | 200 |
| 4/0 AWG | 230 | 230 |
Frequently Asked Questions
Why 125% for continuous loads?
Heat. A breaker loaded to 100% for hours runs hot and can trip early or age fast; the NEC requires continuous loads to be sized at 125% so the breaker cruises at 80%.
Can I put a 20 A breaker on 14 AWG if the insulation is 90°C?
No. 240.4(D) caps 14 AWG at a 15 A breaker no matter the insulation rating. The 90°C column is for derating maths, not for raising the breaker.
The load is between breaker sizes and not continuous. Round up or down?
The breaker must be at least the load; choose the next standard size up, then check the wire allows it.
What about aluminium wire?
This check is copper only. Aluminium ampacities are lower and terminations have extra rules — a separate check, and a licensed electrician's call.