Generator Size Calculator
Generators fail on starting watts, not running watts — the fridge that cruises at 150 W kicks at 1,200. Tick what you need to run and this calculator totals the running load, adds the biggest motor surge honestly, and recommends a size with headroom.
Generator Size Calculator
Results
Total running watts
0 W
Peak watts (required)
0 W
Recommended generator size
0 W
Only the LARGEST motor surge is added — motors rarely all start in the same second, and sizing for every surge at once buys a generator you'll never use.
How It Works
Add up everything's RUNNING watts. Then find the single largest difference between starting and running watts among your motor loads — that's the surge the generator must survive while everything else runs. Required = running total + largest surge. Finally add 20% headroom (running a generator flat-out shortens its life and sags its voltage) and round up to a standard size. Resistive loads — water heaters, kettles — have no surge: starting equals running.
Worked Example
Refrigerator (150/1,200), furnace blower (600/1,200) and a well pump (1,000/2,500): running total 1,750 W. Surges: fridge 1,050, blower 600, pump 1,500 — the pump wins. Required = 1,750 + 1,500 = 3,250 W; with 20% headroom, 3,900 → buy a 4,000 W generator. Add an electric water heater instead (4,500 W, no surge) plus 500 W of lights: 5,000 running, 5,000 required, 6,000 W recommended.
Reference Table
| Appliance | Running W | Starting W |
|---|---|---|
| Refrigerator | 150 | 1,200 |
| Chest freezer | 100 | 800 |
| Well pump (1 hp) | 1,000 | 2,500 |
| Sump pump | 800 | 1,800 |
| Furnace blower (gas) | 600 | 1,200 |
| Central AC (3 ton) | 3,000 | 4,500 |
| Electric water heater | 4,500 | 4,500 |
| Washing machine | 500 | 1,200 |
Frequently Asked Questions
Why not add ALL the starting watts?
Because motors start at different moments. Sizing for simultaneous surges would roughly double the generator for an event that lasts a second and almost never happens; the largest-surge method is the industry standard.
Inverter or conventional generator?
Inverters give cleaner power (safer for electronics) and better fuel economy at partial load; conventional units are cheaper per watt. Size first with this calculator, then choose the type for your loads.
Can I connect it to my house panel?
Only through a transfer switch or interlock installed by a licensed electrician — NEVER by back-feeding a dryer outlet, which can kill line workers and is illegal. Portable units also kill with carbon monoxide: outdoors only, 20 ft from the house, exhaust pointed away.
What about a whole-house standby unit?
Those are sized from your service and managed loads, often 10–24 kW, and installed with an automatic transfer switch by a dealer. This calculator sizes portable and partial-home backup honestly; a standby quote needs the load calculation on our Residential Load page too.
Safety Note
These calculators are planning and estimating aids based on the references shown. They are not a substitute for the current code, local amendments, or a licensed electrician. Verify every result before ordering material or starting work.