Generators fail on starting watts, not running watts — the fridge that cruises at 150 W kicks at 1,200. Tick what you need to run and this calculator totals the running load, adds the biggest motor surge honestly, and recommends a size with headroom.

Generator Size Calculator

Appliances to run

Results

Total running watts

0 W

Peak watts (required)

0 W

Recommended generator size

0 W

Only the LARGEST motor surge is added — motors rarely all start in the same second, and sizing for every surge at once buys a generator you'll never use.

How It Works

Add up everything's RUNNING watts. Then find the single largest difference between starting and running watts among your motor loads — that's the surge the generator must survive while everything else runs. Required = running total + largest surge. Finally add 20% headroom (running a generator flat-out shortens its life and sags its voltage) and round up to a standard size. Resistive loads — water heaters, kettles — have no surge: starting equals running.

Worked Example

Refrigerator (150/1,200), furnace blower (600/1,200) and a well pump (1,000/2,500): running total 1,750 W. Surges: fridge 1,050, blower 600, pump 1,500 — the pump wins. Required = 1,750 + 1,500 = 3,250 W; with 20% headroom, 3,900 → buy a 4,000 W generator. Add an electric water heater instead (4,500 W, no surge) plus 500 W of lights: 5,000 running, 5,000 required, 6,000 W recommended.

Reference Table

ApplianceRunning WStarting W
Refrigerator1501,200
Chest freezer100800
Well pump (1 hp)1,0002,500
Sump pump8001,800
Furnace blower (gas)6001,200
Central AC (3 ton)3,0004,500
Electric water heater4,5004,500
Washing machine5001,200

Frequently Asked Questions

Why not add ALL the starting watts?

Because motors start at different moments. Sizing for simultaneous surges would roughly double the generator for an event that lasts a second and almost never happens; the largest-surge method is the industry standard.

Inverter or conventional generator?

Inverters give cleaner power (safer for electronics) and better fuel economy at partial load; conventional units are cheaper per watt. Size first with this calculator, then choose the type for your loads.

Can I connect it to my house panel?

Only through a transfer switch or interlock installed by a licensed electrician — NEVER by back-feeding a dryer outlet, which can kill line workers and is illegal. Portable units also kill with carbon monoxide: outdoors only, 20 ft from the house, exhaust pointed away.

What about a whole-house standby unit?

Those are sized from your service and managed loads, often 10–24 kW, and installed with an automatic transfer switch by a dealer. This calculator sizes portable and partial-home backup honestly; a standby quote needs the load calculation on our Residential Load page too.

Safety Note

These calculators are planning and estimating aids based on the references shown. They are not a substitute for the current code, local amendments, or a licensed electrician. Verify every result before ordering material or starting work.