Pipe Size Calculator (Fixture Units)
Not everything runs at once — that is the whole insight behind fixture units. Hunter's curve turns a building's total WSFU into the flow it will realistically demand, and velocity picks the pipe. Add up your fixtures below and get both numbers.
Pipe Size Calculator (Fixture Units)
Fixture-count helper (optional)
Add counts to total up WSFU, then copy the sum into the field above.
Helper total: 0 WSFU
Results
Design flow (Hunter)
23 GPM
Recommended pipe size
1¼″ copper (Type L)
5.9 ft/sec (≤ 8 ft/sec)
Next size down
1″ copper (Type L) — 8.9 ft/sec (too fast)
How It Works
Every fixture carries a Water Supply Fixture Unit value reflecting how much water it uses and how often. Summing them and reading Hunter's probability curve gives the design flow — far less than the sum of every fixture's maximum, because they never all run together. Flush-valve systems peak harder than tank systems, so they use a steeper curve. Finally, the pipe is the smallest copper size that carries the design flow at or under 8 ft/sec.
Worked Example
A home totalling 30 WSFU on flush tanks reads 23 GPM on Hunter's curve. Velocity check: ¾-inch runs 15.2 ft/sec (far too fast), 1-inch runs 8.9 (still over), 1¼-inch runs 5.9 — so the main is 1¼-inch copper, even though no single fixture in the house uses more than a ½-inch connection.
Reference Table
Fixture-unit helper values (WSFU):
| Fixture | WSFU |
|---|---|
| Bathroom group (tank) | 6 |
| Bathroom group (flush valve) | 10 |
| Kitchen sink | 2 |
| Dishwasher | 2 |
| Washing machine | 4 |
| Hose bibb | 5 |
| Shower (separate) | 2 |
| Bathtub | 4 |
Frequently Asked Questions
Why is design flow less than the sum of fixtures?
Probability. Hunter's 1940s research (still the basis of both US plumbing codes) showed simultaneous use follows a predictable curve — sizing for everything at once would waste a fortune in oversized pipe.
Tank or valve — how do I know?
Homes are almost always flush tanks. Commercial washrooms with exposed flushometers are flush valves, and their sharp peaks demand more flow at the same WSFU.
Does this size the whole system?
It sizes a main or branch carrying the WSFU you enter. Individual fixture connections still follow code minimums, and long runs may need a pressure-loss check beyond velocity.
WSFU or FU — same for drainage?
No. Drainage fixture units (DFU) are a different table for sizing drains and vents. This calculator is water supply only.