Toolbox Calculator

Australian Cable Size Calculator

Long Aussie runs — the shed, the granny flat, the back fence — are where cables fail on voltage drop while the ampacity looked fine. This calculator checks both gates the AS/NZS 3008 way: capacity against the breaker, and total drop against the 5% rule in AS/NZS 3000.

Australian Cable Size Calculator

Single-phase 230V, copper V75, unenclosed in air (touching), per AS/NZS 3008 tables. AS/NZS 3000 limits voltage drop to 5% of 230V (11.5V) from the point of supply — in practice part of the 5% is used by the consumer mains, so many designers work to less on the final subcircuit.

Results

—

How It Works

Pick the protective device first (smallest standard rating at or above the design current), then the cable’s tabulated capacity must at least match it. Voltage drop uses the AS/NZS 3008 Vc figures: drop = Vc × current × length ÷ 1,000, and the installation’s total drop from the point of supply must stay within 5% of 230 V (11.5 V). The capacities here are for copper V75 unenclosed in air; enclosed, buried or grouped cables rate lower.

Worked Example

A 10 A load on a 50 m run: a 1.5 mm² cable carries 16 A, so ampacity passes easily — but the drop is 28.35 × 10 × 50 ÷ 1,000 = 14.2 V, well over 11.5 V. Step to 2.5 mm² and the drop falls to 8.5 V: result 2.5 mm², set by voltage drop.

Reference Table

Cable data — size → capacity (A) / Vc voltage-drop mV/A/m (single-phase):

Cable sizeCapacity (A)Vc (mV/A/m)
1.5 mm²1628.35
2.5 mm²2217.03
4 mm²2910.62
6 mm²377.12
10 mm²514.30
16 mm²682.68
25 mm²911.71

Frequently Asked Questions

Why 5%?

AS/NZS 3000 caps voltage drop from the point of supply to any point in the installation at 5%. Consumer mains use part of that allowance, which is why designers often target 2–3% on a long final subcircuit.

What does V75 mean?

The insulation’s temperature rating — 75°C PVC, the standard building wire in Australia. V90 and XLPE cables have different capacities and drop figures.

Can I use this for a three-phase motor?

No — single-phase only. Three-phase drop and starting currents need their own calculation.

Who can install cable in Australia?

Only a licensed electrician — Australia does not have a DIY electrical category. This calculator is for planning and quoting, not installation guidance.

Safety Note

These calculators are planning and estimating aids based on the references shown. They are not a substitute for the current code, local amendments, or a licensed electrician. Verify every result before ordering material or starting work.