UK Cable Size Calculator
UK cable sizing has two gates, and the second one catches people out: the cable must carry the current, and the voltage drop over the run must stay inside BS 7671 limits — 3% for lighting, 5% for everything else. Long runs to garages and garden buildings fail on drop long before they fail on ampacity. Check both here.
UK Cable Size Calculator
Single-phase 230V, copper, 70°C PVC, Installation Method C (clipped direct), per BS 7671 tables.
Results
—
How It Works
The protective device is chosen first: the smallest standard rating at or above your design current. The cable must then have a tabulated capacity (Iz, here for Method C — clipped direct) at least equal to that device rating, so the device protects the cable. Separately, voltage drop = the cable’s mV/A/m figure × current × length; at 230 V the limits are 6.9 V for lighting and 11.5 V for other circuits. The recommended cable is the smallest that passes both gates.
Worked Example
A 32 A design current over a 40 m run (other circuit): the device is 32 A. A 4 mm² cable carries 36 A — gate one passed — but its drop is 11 × 32 × 40 ÷ 1,000 = 14.1 V, over the 11.5 V limit. The 6 mm² drops 9.3 V and carries 46 A: result 6 mm², sized by voltage drop, not by ampacity.
Reference Table
Cable data — size → Iz Method C (A) / voltage-drop mV/A/m:
| Cable size | Iz, Method C (A) | Voltage drop (mV/A/m) |
|---|---|---|
| 1.0 mm² | 15 | 44 |
| 1.5 mm² | 19.5 | 29 |
| 2.5 mm² | 27 | 18 |
| 4 mm² | 36 | 11 |
| 6 mm² | 46 | 7.3 |
| 10 mm² | 63 | 4.4 |
| 16 mm² | 85 | 2.8 |
| 25 mm² | 112 | 1.75 |
Frequently Asked Questions
What is Method C?
Cable clipped directly to a surface — the most common reference method for domestic work. Other methods (buried, in conduit, in insulation) have different capacities; insulation in particular can halve them.
Why is lighting limited to 3%?
Lights make voltage drop visible — dimming and flicker — so BS 7671 holds lighting circuits to 3% while allowing 5% for other uses, measured from the origin of the installation.
Does this cover three-phase?
No — this calculator is single-phase 230 V only. Three-phase uses different drop figures (× √3 relationships) and balanced-load assumptions.
My cable is in thermal insulation. Can I still use this?
No. Insulation derating is severe (a cable fully surrounded by insulation may be rated at half). Use the BS 7671 correction factors or ask your electrician.
Safety Note
These calculators are planning and estimating aids based on the references shown. They are not a substitute for the current code, local amendments, or a licensed electrician. Verify every result before ordering material or starting work.